Flamefast Heat Treatment Gas Detection Systems Gas Proving System Health & Safety Project Services Used Equipment Schemes of Work Contact Us

 

Gas Detection

Toxic Gas Detector

Toxic Gas Detector• 2-wire, 4-20mA Transmitter
• Plug-in electrochemical sensor
• Built-in ZERO & SPAN controls
• One person calibration
• SMD electronic circuitry
• Enhanced RFI and EMI resistance
• Cost effective with high performance
• Works with most 4-20mA controllers
• Calibration gas ampoules available
• Certified ATEX Eex ia IIC T4

The T100 is a 4-20mA 2-wire transmitter can measure a wide range of gases and is housed in a rugged, compact metallic enclosure. It incorporates advanced SMD electronics and a 3 electrode electrochemical sensor based on micro fuel cell technology, designed to be maintenance free and inherently stable.

The sensor uses the highly successful capillary diffusion barrier technology, resulting in a low temperature coefficient and a direct response to concentration, relatively unaffected by pressure. The use of electrodes based on fuel cell technology gives a high reserve of activity which results in long term stability.

Gas diffusing to the sensor electrode reacts at the surface of the electrode either by oxidation (e.g. CO, H2S, SO2, NO, H2, HCN, HCl, C2H4O, NH3) or by reduction (NO2, O3 and Cl2). Reactions are catalysed by specially developed electrode materials and are designed to be specific to the gas being sensed.

T100 Specifications
Supply voltage Nominal 24Vdc (operates from 12Vdc to 30Vdc)
Supply current Normal: 4mA, full-scale 20mA
Ec-cell operating life in air at S.T.P. Minimum 2 years (1 year for NH3)
Preconditioning Requirements 1 Hour (24 hours for HCl, C2H4O, NO & NH3)
Storage life at 0 to 20°C 6 months
Operating temperature range -10° to +40°C (H2S, -40°C to +40°C)
Operating pressure range Ambient ± 10%
Effect of operating pressure on accuracy > 0.05% signal per mm Hg
Operating RH range 15% to 90% non-condensing
Position sensitivity None
Drift, S.T.P. continuous duty in air <2% Full Scale per month
CENELEC approval Eex ia IIC T4 (Certificate No. Ex 99E2035)
Size W: 75mm, D: 58mm, H: 80mm (excluding sensor)
Weight 400g
Electromagnetic Conformance (EMC) Complies with EN50081 and EN50082
Enclosure material Durable aluminium ALSi12, magnesium content <0.4%,
finished in stove enamel gray RAL7001, rated IP65.
(Marine grade version available to special order)

Available gases and ranges

To cover a wide range of applications, a variety of ranges are available. The following table shows the available gases along with the minimum and maximum full-scale range for that gas. The maximum T90 response time is also shown (in seconds).

Gas CO H2S SO2 NO NO2 H2 Cl2 HCN HCl NH3 O3 C2H4O O2
Min FSD (ppm) 50 5 5 10 5 50 5 50 5 50 3 20 5%
Max FSD (ppm) 4% 1000 2000 1500 200 4% 250 200 100 200 5 100 25%
T90 Response 25 30 15 10 35 30 100 100 120 100 150 140 12

Product Datasheet

None Available

Download Acrobat Reader

All our data sheets can be downloaded in .PDF format.

To view them, you need Adobe® Acrobat® Reader 4.0 or later. If you do not have Adobe® Acrobat® Reader 4.0 or later versions, you can download for free...

Get Acrobat Reader


If you have any questions about downloading our datasheets, please do not hesitate to contact us at sales@flamefast.co.uk